SRC-4 Installation and Operation Manual
INSTALLATION
Configuration Dip-switch Setup
The configuration dip-switch package (SW1) is located on front panel of the SRC-4.
Note: After changing any dip-switch, please repower the unit.
SW1-1 Baud Rate
OFF = 9600 (default)
ON = Auto-Detect
In auto-detect mode the SRC-4 can automatically detect and set itself to the baud
rate a connected serial device. This allows the SRC-4 to be used with a wide range
of serial devices.
To use the Auto-Detect feature power down the SRC-4, turn SW1-1 on, and connect
the serial device you wish to interface with. Configure the serial device to send an
uppercase U. Power up the SRC-4, from power up there is a 3 second window in
which a received U will set the SRC-4’s baud rate. Once the baud rate is detected
and set the SRC-4 will send its version information over the serial port. After SRC-
4’s baud rate has been set it will retain this setting until the auto-detect feature is
used again.
SW1-2 Unused
SW1-3 SW1-4 Operation Mode
OFF OFF Computer (default)
ON OFF Pair Mode
OFF ON Data Mode
ON ON Data Programming Mode
Computer Operation Mode
In computer operation mode the SRC-4 uses the following ASCII string command
format:
Relay Control Commands:
*0OR1L = Latch relay 1
*0OR1F = Unlatch relay 1
*0OR1P = Pulse relay 1
*0OR2L = Latch relay 2
*0OR2F = Unlatch relay 2
*0OR2P = Pulse relay 2
*0OR3L = Latch relay 3
*0OR3F = Unlatch relay 3
*0OR3P = Pulse relay 3
*0OR4L = Latch relay 4
*0OR4F = Unlatch relay 4
*0OR4P = Pulse relay 4